• 48043 - circuit breaker Masterpact NW16H1 - 1600 A - 3 poles - fixed - w/o trip unit, Schneider Electric
MAIN CHARACTERISTICS
range
MASTERPACT
range of product
MASTERPACT NW
product name
MASTERPACT NW
product or component type
BASIC FRAME
device short name
MASTERPACT NW16
circuit breaker name
MASTERPACT NW16H1
poles description
3P
breaking capacity code
H1
suitability for isolation
YES CONFORMING TO IEC 60947-2
COMPLEMETARY CHARACTERISTICS
mounting mode
FIXED
[In] rated current
1600 A 40 DC
[Ui] rated insulation voltage
1000 V AC 5060 HZ CONFORMING TO IEC 60947-2
[Uimp] rated impulse withstand voltage
12 KV CONFORMING TO IEC 60947-2
[Icm] rated short-circuit making capacity
143 KA 525 V AC 5060 HZ
[Ue] rated operational voltage
690 V AC 5060 HZ CONFORMING TO IEC 60947-2
breaking capacity
65 KA ICU AT 525 V AC 5060 HZ CONFORMING TO IEC 60947-2
[Ics] rated service breaking capacity
ICS 65 KA 525 V AC 5060 HZ CONFORMING TO IEC 60947-2
protection type
WITHOUT PROTECTION
mechanical durability
12500 CYCLES WITHOUT MAINTENANCE CONFORMING TO IEC 60947-2
electrical durability
10000 CYCLES 440 V AC 5060 HZ WITHOUT MAINTENANCE CONFORMING TO IEC 60947-2
[Icw] rated short-time withstand current
36 KA 3 S CONFORMING TO IEC 60947-2
maximum breaking time
25 MS
closing response time
< 70 MS
height
352 MM
width
422 MM
depth
297 MM
compatibility code
NW16

48043 - circuit breaker Masterpact NW16H1 - 1600 A - 3 poles - fixed - w/o trip unit, Schneider Electric