• 48116 - circuit breaker Masterpact NW50H2 - 5000 A - 4 poles - fixed - w/o trip unit, Schneider Electric
MAIN CHARACTERISTICS
range
MASTERPACT
range of product
MASTERPACT NW
product name
MASTERPACT NW
product or component type
BASIC FRAME
device short name
MASTERPACT NW50
circuit breaker name
MASTERPACT NW50H2
poles description
4P
neutral position
LEFT
network type
AC
breaking capacity code
H2
suitability for isolation
YES CONFORMING TO IEC 60947-2
utilisation category
B
COMPLEMETARY CHARACTERISTICS
network frequency
50 60 HZ
control type
PUSHBUTTON
mounting mode
FIXED
[In] rated current
5000 A 40 DC
[Ui] rated insulation voltage
1000 V AC 5060 HZ CONFORMING TO IEC 60947-2
[Uimp] rated impulse withstand voltage
12 KV CONFORMING TO IEC 60947-2
[Icm] rated short-circuit making capacity
220 KA 690 V AC 5060 HZ
[Ue] rated operational voltage
690 V AC 5060 HZ CONFORMING TO IEC 60947-2
circuit breaker CT rating
5000 A
breaking capacity
150 KA ICU AT 220...240 V AC 5060 HZ CONFORMING TO IEC 60947-2
[Ics] rated service breaking capacity
ICS 100 KA 690 V AC 5060 HZ CONFORMING TO IEC 60947-2
protection type
WITHOUT PROTECTION
mechanical durability
10000 CYCLES WITH MAINTENANCE CONFORMING TO IEC 60947-2
electrical durability
AC-3 : 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
connection pitch
230 MM
[Icw] rated short-time withstand current
100 KA 1 S CONFORMING TO IEC 60947-2
integral instant protection
243...297 KA
maximum breaking time
25 MS
closing response time
< 80 MS
height
352 MM
width
997 MM
depth
297 MM
compatibility code
NW50

48116 - circuit breaker Masterpact NW50H2 - 5000 A - 4 poles - fixed - w/o trip unit, Schneider Electric

  • € 10,663.92 Ex Tax: