• 50492 - insulation monitoring XML308 Vigilohm - 380..415 V AC 50/60 Hz - fail safe, Schneider Electric
MAIN CHARACTERISTICS
range of product
VIGILOHM
device short name
XML308
type of measurement
NT RTC E LKG C LCL MSREMENT
signal contacts composition
3 C O
earthing system
IT
display type
LCD
scale
0.1..999 KOHM
number of channels
8
measurement current
0...5 MA
measurement voltage
6 V
fail safe feature
WITH
[Us] rated supply voltage
380...415 V AC 5060 HZ TOLERANCE - 15...10
mounting position
HORIZONTAL MOUNTING
COMPLEMETARY CHARACTERISTICS
[Ue] rated operational voltage
<= 1000 V AC 45...400 HZ DEVICE CONNECTED TO PHASE WITH PHT1000 SUBASSEMBLY
signalling function
ALARM
polling time
15 S
test function
MANUAL SELF TEST
breaking capacity
10 A AT 24 V DC LR = 1 MS
power consumption in VA
<= 30 VA
mounting mode
FLUSH-MOUNTED
mounting support
CUBICLE
height
129 MM
width
229 MM
depth
213.5 MM
product weight
4.5 KG
tamperproof of settings
PROTECTED BY ACCESS CODE
auxiliary connection terminal
TUNNEL TYPE TERMINALS CABLE CROSS SECTION 0.75...1.5 MM FLEXIBLE
market segment
RESIDENTIAL
compatibility code
XML308

50492 - insulation monitoring XML308 Vigilohm - 380..415 V AC 50/60 Hz - fail safe, Schneider Electric