• LC1D183JD - TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 18 A - 12 V DC coil, Schneider Electric
MAIN CHARACTERISTICS
range of product
TESYS D
range
TESYS
product name
TESYS D
product or component type
CONTACTOR
device short name
LC1D
contactor application
MOTOR CONTROL
utilisation category
AC-1
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
<= 690 V AC 25...400 HZ FOR POWER CIRCUIT
[Ie] rated operational current
18 A <= 60 C AT <= 440 V AC AC-3 FOR POWER CIRCUIT
motor power kW
4 KW AT 220...230 V AC 5060 HZ AC-3
motor power HP (UL / CSA)
1 HP AT 115 V AC 5060 HZ FOR 1 PHASE MOTORS
control circuit type
DC STANDARD
[Uc] control circuit voltage
12 V DC
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 KV CONFORMING TO IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
25 A AT <= 60 C FOR POWER CIRCUIT
Irms rated making capacity
140 A AC FOR SIGNALLING CIRCUIT CONFORMING TO IEC 60947-5-1
rated breaking capacity
300 A AT 440 V FOR POWER CIRCUIT CONFORMING TO IEC 60947
[Icw] rated short-time withstand current
145 A <= 40 C 10 S POWER CIRCUIT
associated fuse rating
10 A GG FOR SIGNALLING CIRCUIT CONFORMING TO IEC 60947-5-1
average impedance
2.5 MOHM AT 50 HZ - ITH 25 A FOR POWER CIRCUIT
[Ui] rated insulation voltage
690 V FOR POWER CIRCUIT CONFORMING TO IEC 60947-4-1
electrical durability
1.65 MCYCLES 18 A AC-3 AT UE <= 440 V
power dissipation per pole
2.5 W AC-1
safety cover
WITH
mounting support
PLATE
standards
CSA C22.2 NO 14
product certifications
BV
connections - terminals
control circuit : spring terminals 1 cable(s) 2.5 mm² - cable stiffness: flexible - without cable end
operating time
53.55..72.45 MS CLOSING
safety reliability level
B10D = 1369863 CYCLES CONTACTOR WITH NOMINAL LOAD CONFORMING TO ENISO 13849-1
mechanical durability
30 MCYCLES
operating rate
3600 CYCH AT <= 60 DC
COMPLEMETARY CHARACTERISTICS
coil technology
W INTEGRAL SUPPRESSION DEVICE
control circuit voltage limits
0.1...0.25 UC DROP-OUT AT 60 C DC
time constant
28 MS
inrush power in W
5.4 W AT 20 DC
hold-in power consumption in W
5.4 W AT 20 DC
auxiliary contacts type
TYPE MECHANICALLY LINKED 1 NO + 1 NC CONFORMING TO IEC 60947-5-1
signalling circuit frequency
25..400 HZ
minimum switching current
5 MA FOR SIGNALLING CIRCUIT
minimum switching voltage
17 V FOR SIGNALLING CIRCUIT
non-overlap time
1.5 ms on de-energisation between NC and NO contact
insulation resistance
> 10 MOHM FOR SIGNALLING CIRCUIT
contact compatibility
M4
compatibility code
LC1D

LC1D183JD - TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 18 A - 12 V DC coil, Schneider Electric